Duke FLEXIBLE BATCH BROILER Specifications Page 71

  • Download
  • Add to my manuals
  • Print
  • Page
    / 90
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 70
Troubleshooting
Step 7 Components
Troubleshooting
Step 7 Components
Controller-See slide #74 or #79
Conveyor Motor Relay
Input Voltage Check
24 VDC across wires 30 & 31
from controller
Output Voltage Check
120 VAC across wires 4 & 5
Other Relay Tests
-With 24 VDC input there should be 120 VAC across the output
-With 0 VDC input there should be approx. 0 VAC across output
Motor Capacitor
Test: Discharge capacitor.
Resistance should measure low and drift to high ohms
Page view 70
1 2 ... 66 67 68 69 70 71 72 73 74 75 76 ... 89 90

Comments to this Manuals

No comments